Skip to main content

266 products · PKR prices · Updated November 2026

Contactors & Motor StartersPrice in Pakistan

Shop genuine contactors & motor starters from Chint, Schneider Electric, LS and Siemens at EU Enterprise, Lahore. Prices range from Rs 472 to Rs 450,000. Order online or on WhatsApp with Cash on Delivery across Pakistan.

Showing 1–12 of 266 products · Page 1 of 23

Contactors & Motor Starters buying guides

Contactors & Motor Starters Price List in Pakistan (November 2026)

Prices in PKR · Updated November 2026

Contactors & Motor Starters Price List in Pakistan (November 2026)
ProductPrice
LS GMC-22 Magnetic Contactor 3poleRs 1,500
FUJI AC Magnetic Contactor Sc-03 20A in Lot Good ConditionRs 1,875
FUJI Magnetic Contactor Sc-0 20ARs 2,150
SC-05 13A Imported Fuji Fe Electromagnetic AC ContactorRs 1,600
SC4-0 Imported Fuji Fe Electromagnetic AC Contactor 25ARs 1,650
SC4-1 Imported Fuji Fe Electromagnetic AC Contactor 32ARs 2,500
SC-5-1 Imported Fuji Fe Electromagnetic AC contactor 32ARs 3,750
50A SC-N1 Fuji magnetic Contactor RefurbishRs 7,000
SC-N2 Imported Fuji Fe Electromagnetic AC Contactor 60ARs 9,000
SC-N2s Imported Fuji Fe Electromagnetic AC Contactor 80ARs 9,000
SC-N3 Imported Fuji Fe Electromagnetic AC Contactor 100A JapanRs 26,240
LS Electric MC-9b Sol ContactorRs 1,680

About Contactors & Motor Starters

Contactors switch motors, heaters and other power loads under the control of a low-current coil. Together with overload relays, motor protection circuit breakers and timers they make up the motor starters found in almost every industrial panel.

Choosing a contactor means matching the load category, the coil voltage and the protection, not only the motor kilowatts.

How to choose

  • Size by AC-3: for squirrel-cage motors use the AC-3 rating (kW or amps at 400 V). The higher AC-1 figure is for resistive loads, and jogging or plugging duty (AC-4) needs a larger contactor.
  • Coil voltage: 24 V DC for PLC-driven circuits, 230 V AC for the most common control circuits, others as required.
  • Overload protection: a thermal or electronic overload relay set to the motor’s nameplate current, or a motor protection circuit breaker that combines short-circuit and overload protection.
  • Starter type: direct-on-line (DOL) for smaller motors, star-delta or a soft starter for larger ones to limit starting current, and mechanically interlocked pairs for reversing. Star-delta needs a six-terminal motor wound for 400 V delta and gives about one-third of the direct starting torque.
  • Auxiliary contacts, surge suppressors and mounting accessories complete the starter.

Contactors & Motor Starters: frequently asked questions

What is the difference between a contactor and a relay?

A contactor has heavy main contacts and arc control for switching power loads such as motors. A relay switches low-current control signals.

What should I set the overload relay to?

The full-load current on the motor nameplate. In a star-delta starter, set it to the nameplate current if the relay is in the supply line, or to about 58% (1/√3) only if it is wired in series with the delta windings. Follow the starter’s wiring diagram.

Do I need a motor protection circuit breaker?

Not always. A motor protection circuit breaker combines short-circuit and overload protection in one device, so for small and medium motors it replaces the fuse or breaker plus overload relay. Larger motors usually use an MCCB with a separate overload relay.