Buying guide
Flood Light Wattage and High Bay Lumens: How Much Light a Space Needs
Choose a flood light or high bay by the light it gives, not by its watts. Multiply the target illuminance in lux by the floor area, divide by the utilisation and maintenance factors (together often about 0.5) to get the lumens needed, then divide by the fittings’ lumens per watt to find the wattage. A 600 m² workshop lit to 300 lux, for example, needs about 370,000 lm, or roughly 2.6 kW of 140 lm/W high bays.
The short answer
- Lumens, not watts. Watts are what a fitting draws; lumens are the light it gives. Good LED high bays give about 130–160 lm/W and floods about 100–150 lm/W.
- Target lux – about 100–200 for storage, 300 for packing, welding and machining, 500 for fine work and 20–50 for outdoor yards (EN 12464-1:2021 and EN 12464-2:2014; check the current editions).
- Lumens needed = lux × area ÷ (UF × MF). UF × MF is often about 0.5, so you need roughly 2 × lux × m² lumens; more in tall, narrow or dirty spaces.
- Spacing – up to about 1 to 1.5 times the height above the working plane, or the datasheet limit if lower.
- Site ratings – IP65 or more, a temperature rating that covers a hot roof, a stated surge rating, and MCBs chosen for driver inrush.
Watts, lumens and target lux
Luminous efficacy links watts and lumens: lumens = watts × lm/W. A 150 W fitting at 140 lm/W gives 21,000 lm; at 100 lm/W only 15,000 lm, so you need 40 percent more fittings. Compare the rated lumens of the complete fitting, not the LED chip figure.
Standards give maintained illuminance: the average must not fall below it, even just before cleaning. They are recommendations; local codes or client specifications may differ.
| Space or task | Lux | Source |
|---|---|---|
| Store room, occasional / continuous use | 100 / 200 | EN 12464-1 |
| Rack aisles with people (floor level) | 150 | EN 12464-1 |
| Unloading and loading areas | 200 | EN 12464-1 |
| Packing, welding, rough machining | 300 | EN 12464-1 |
| Fine assembly, precision machining | 500 | EN 12464-1 |
| Yard: occasional / continuous loading | 20 / 50 | EN 12464-2:2014 |
| Yard: reading labels, covered loading | 100 | EN 12464-2:2014 |
Indoor values are the “required” (minimum) column of EN 12464-1:2021; its higher “modified” column (for example 500 lux for welding, rough machining and packing) applies when the task is critical, errors are costly, the work is long or eyesight is below normal. Outdoor values come from the 2014 tables of EN 12464-2, revised in 2024, so check the current edition. In workshops the darkest point should be at least 0.6 of the average (0.4 in storage areas).
How many fittings: the lumen method
N = E × A ÷ (Φ × UF × MF), where N is the number of fittings, E the target lux, A the area in m² and Φ the rated lumens of one fitting.
- Utilisation factor (UF) – the share of lumens reaching the working plane, read from the maker’s table for the surface reflectances and the room index k = L × W ÷ (Hm × (L + W)), with Hm the height of the fittings above the working plane. For one wide-beam high bay and medium to dark surfaces it is about 0.5 at k = 1, 0.7 at k = 2 and 0.85 at k = 3.
- Maintenance factor (MF) – light lost to ageing and dirt. For sealed LED fittings use about 0.8 in clean areas, 0.7 in a typical workshop or warehouse and 0.6 or less with heavy dust or rare cleaning. If conditions are unknown, one major maker uses 0.57 for normal industrial rooms.
Worked example: a 600 m² workshop
A 30 m × 20 m workshop needs 300 lux for welding and machining. The fittings hang at 7 m above 0.85 m benches, so Hm = 6.15 m. Sealed IP65 high bays will be cleaned once a year.
- k = 600 ÷ (6.15 × 50) = 1.95, so UF = 0.7 from a typical table; take MF = 0.7.
- A 150 W high bay at 140 lm/W gives 21,000 lm.
- N = 300 × 600 ÷ (21,000 × 0.7 × 0.7) = 17.5, so 18 fittings: 2.7 kW, or 4.5 W/m².
- Six rows of three give 5.0 m × 6.7 m spacing, within 1.5 × 6.15 = 9.2 m, with 2.5 m and 3.3 m to the walls. Result: 309 lux maintained, about 440 lux when new.
This gives only the average; for evenness and glare, ask for a point-by-point layout from the maker’s photometric file.
Worked example: an outdoor loading yard
A 30 m × 20 m yard where lorries are loaded every night needs 50 lux. With no walls or ceiling to reflect light, and some spill past the edges, assume UF 0.4, and MF 0.7 for sealed IP66 floods.
- Lumens needed: 50 × 600 ÷ (0.4 × 0.7) = 107,000 lm.
- A 150 W flood at 130 lm/W gives 19,500 lm: 107,000 ÷ 19,500 = 5.5, so six floods (900 W), for example three on each long side at 8 m or more, aimed so the beams overlap without dazzling drivers. Confirm this first estimate with a layout.
Mounting height, spacing and beam angle
| Type | Typical mounting | Usual beam | Typical use |
|---|---|---|---|
| Low bay | About 3–6 m | Wide, about 90–120° | Low-roof workshops, stores |
| High bay | About 6–12 m or more | 60–120°; narrower for aisles | Factories, warehouses |
| Flood light | Walls or poles, often 6–12 m | Narrow, wide or asymmetric | Yards, car parks, facades |
Start with wide-beam fittings no further apart than about 1 to 1.5 times their height above the working plane, never beyond the maximum spacing-to-height ratio (SHR max) on the datasheet, and about half that spacing from the walls. Narrow beams need closer spacing but reach down tall aisles; wide beams suit low roofs. Indoors, avoid tilted floods, which cause glare.
IP, IK, heat and lifetime ratings
| Rating | What it means | Typical use |
|---|---|---|
| IP65 | Dust-tight; water jets | Outdoor floods; dusty or damp halls |
| IP66 | Dust-tight; powerful water jets | Exposed yards, monsoon rain, hosing (IP69K for hot high-pressure washdown) |
| IP67 | Dust-tight; immersion to 1 m for 30 min | Pooling water; jets only if also IP66 |
| IK07 / IK08 | 2 J / 5 J impact | High bays / floods within reach |
| IK10 | 20 J impact | Sports halls, forklift areas |
Heat. Datasheets give ta, the highest ambient for safe operation (25 °C if unmarked), and tq, the ambient at which lumen and life figures apply. Lahore reaches about 45 °C in the shade in heatwaves, and air under a metal roof is hotter, so choose a ta of at least 50 °C.
Lumen maintenance. L80 at 50,000 h means at least 80 percent of the initial lumens remain after 50,000 hours, usually as a median (B50) value; L70 allows more loss. Good high bays quote L80 or better at 50,000 h at a tq of 25–35 °C. These are projections, not measurements.
Colour temperature and colour rendering
4000 K and 5000 K both suit factories: 5000 K looks crisper, 4000 K softer next to offices. 6500 K looks bluish, can feel harsh at night and often adds little or no efficacy. Use Ra 80 or more where people work, as EN 12464-1:2021 asks for most industrial tasks, and Ra 90 at 4000–6500 K for colour inspection. Ra 70 suits circulation routes, where it asks only Ra 40; loading areas where people work ask Ra 80.
Drivers, circuits and switching
- Surge and supply. The basic immunity test for lighting (IEC 61547) is only 1 kV line to line and 2 kV line to earth. Better drivers state higher ratings, often 4 kV on high bays and 6–10 kV on outdoor floods (state line to line or line to earth when you compare), plus a surge protective device (SPD) in the board feeding outdoor circuits, a power factor of 0.9 or more and a wide input range, such as 90–305 V AC.
- Flicker. Poor drivers ripple at 100 Hz, which can make rotating machines look slower or stopped. Ask for flicker data. As a benchmark, EU ecodesign rules for mains LED lamps set PstLM 1.0 and SVM 0.4 (industrial and outdoor products are exempt from SVM). Spread neighbouring fittings over the three phases.
- Inrush sets the MCB count. A typical 150 W driver draws a 50 to 65 A pulse at switch-on, and its maker may allow only about 4 per B16 or 6 to 8 per C16 MCB, not the 20 its running current suggests. Follow the datasheet table, and never raise the MCB rating to fit more drivers: the cable, derated for 45 °C, must still be protected (see MCB vs MCCB vs RCCB). With such drivers the workshop needs three C16 circuits, one per phase.
- Contactors and RCDs. Size a lighting contactor from the maker’s lamp or LED-driver rating, not its AC-1 (heater) rating, since inrush can weld contacts, and let the timer or photocell drive its coil (see relay vs contactor vs SSR). Driver earth leakage (under 0.75 mA each on that driver) adds up, so limit the fittings per RCD.
Buying checklist
- Area, mounting height, task, target lux and evenness.
- Lumens needed = lux × area ÷ (UF × MF), with UF from the maker’s table.
- Datasheet lumens, number of fittings and a layout within the spacing limit.
- Beam to suit the height; asymmetric optics for yards.
- IP65 or more (IP66 on exposed sites), IK08 where fittings can be hit, and a ta for summer heat.
- Ra 80 or more and one colour temperature, usually 4000 K or 5000 K.
- Driver surge rating, power factor, input range, flicker, and L80 at a stated tq.
- Drivers per MCB from inrush data, contactor lamp rating, RCD leakage, SPD and balanced phases.
Browse our flood and high bay lights, plus circuit breakers, contactors and cables for the lighting circuits. Send us the area, mounting height, task and photos of the space on WhatsApp and our team will help you choose.
Frequently Asked Questions
How many watts of flood light do I need?
It depends on the area, the light level the task needs and the efficacy of the floods, not on watts alone. Work out lumens first: lux × area ÷ (utilisation factor × maintenance factor). For example, a 600 m² yard lit to 50 lux, with factors of 0.4 and 0.7, needs about 107,000 lm. At 130 lm/W that is about 820 W, so six 150 W floods. Reading labels or inspection needs more light; car parks need less.
How many lux or lumens does a warehouse need?
EN 12464-1 recommends about 100 lux for store rooms with occasional access, 150 lux for rack aisles where people work, 200 lux for store rooms in continuous use and for unloading and loading areas, and 300 lux for packing and dispatch. Local codes or client specifications may differ. To turn lux into lumens, multiply by the floor area and divide by the utilisation and maintenance factors, often about 0.5 together, so 1,000 m² at 150 lux needs roughly 300,000 lm.
How far apart should high bay lights be?
For wide-beam high bays, a common starting point is a spacing of no more than about 1 to 1.5 times the height of the fittings above the working plane, and never more than the maximum spacing-to-height ratio on the datasheet. Fittings 8 m above a warehouse floor would sit about 8 to 12 m apart at most, with about half that spacing to the walls. Narrow beams need closer spacing, and the lux target often calls for a closer grid anyway.
What is the difference between a high bay and a flood light?
A high bay hangs under the roof and shines straight down with a symmetric beam, usually from about 6 m upwards, to light factory and warehouse floors evenly. A flood light has a bracket so it can be aimed, usually from a wall or pole, to light yards, car parks and facades, and comes with narrow, wide or asymmetric optics. Floods tilted indoors tend to cause glare, so use high bays or low bays for indoor ceiling grids.
Which IP rating does an outdoor flood light need?
IP65 is the usual minimum outdoors: it is dust-tight and protected against water jets, so it copes with rain and dust. Choose IP66 for exposed sites, heavy monsoon rain or areas that are hosed down, since it is tested with powerful jets. IP67 covers temporary immersion but is not tested against jets unless it is also marked IP66. The cable glands and any junction box must be rated as high as the fitting, or water gets in there.
Is 5000 K or 6500 K better for a factory?
For most factories, 5000 K or 4000 K is the better choice. 5000 K looks crisp and close to daylight, which suits workshops and inspection areas, while 4000 K feels softer in mixed areas with offices. 6500 K looks bluish, can feel harsh at night and often gives little or no extra efficacy. Colour rendering matters more for accuracy: choose Ra 80 or higher where people work, and Ra 90 with 4000 to 6500 K for colour inspection.